3/4 HP Motor — How Many Amps?

A 3/4 HP motor draws 6.9A at 240V (single phase) or 2.8A at 240V 3-phase. Wire: 14 AWG, Breaker: 15A. Common uses: Well pump, pool pump, furnace blower.

3/4 HP Motor Amps
6.9A @ 240V 1φ
120V 1-Phase
13.8A
240V 1-Phase
6.9A
240V 3-Phase
2.8A
Wire Size
14 AWG
Breaker
15A
Horsepower
0.75 HP

3/4 HP Motor Wiring Guide — NEC 430

Motor circuits must comply with NEC Article 430. Key requirements for a 3/4 HP motor:

NEC 430.22 — Conductor Sizing: Branch circuit conductors must carry at least 125% of the motor full-load amps (FLA). For this 3/4 HP motor at 240V: 6.9A × 1.25 = 8.6A minimum conductor ampacity. Use 14 AWG copper per NEC Table 310.16.

NEC 430.52 — Branch Circuit Protection: For inverse-time breakers, maximum overcurrent protection is 250% of FLA: 6.9A × 2.5 = 17A. Standard breaker: 15A.

NEC 430.32 — Overload Protection: Motor overload protection must not exceed 125% of motor nameplate FLA. A thermal overload relay or electronic overload is typically built into the motor starter.

Common applications: Well pump, pool pump, furnace blower. Use our Wire Size Calculator and Voltage Drop Calculator for exact conductor sizing.

HP to Amps Reference Table

HP240V 1φ240V 3φWireBreaker
1/2 HP4.9A2A14 AWG15A
3/4 HP6.9A2.8A14 AWG15A
1 HP8A3.6A12 AWG20A
1.5 HP10A4.8A12 AWG20A
2 HP12A5.6A10 AWG25A
3 HP17A9.6A10 AWG30A
5 HP28A15.2A8 AWG40A
7.5 HP40A22A6 AWG50A
10 HP50A28A6 AWG60A
15 HP80A42A3 AWG100A
20 HP100A54A1 AWG125A
25 HP130A68A1/0 AWG150A
30 HP150A80A2/0 AWG175A
40 HP200A104A3/0 AWG250A
50 HP250A130A4/0 AWG300A

Disclaimer: Values from NEC Tables 430.248 and 430.250. Always check motor nameplate for actual FLA. Consult a licensed electrician.