200 Amp Breaker — Wire Size, Max Load & NEC Guide

A 200 Amp breaker requires 3/0 AWG copper wire. Max continuous load: 160A (80% rule). Max watts: 19,200W at 120V or 38,400W at 240V.

200 Amp Breaker Specifications
3/0 AWG Wire
Breaker
200A
Wire Size
3/0 AWG
Max Continuous
160A
Max Watts (120V)
19,200W
Max Watts (240V)
38,400W
Long Run Wire
4/0 AWG
NEC Reference
NEC 230.79

200 Amp Breaker — Complete NEC Guide

200A is the standard modern residential service. Sufficient for most homes including EV charging, electric cooking, and HVAC. Requires 3/0 AWG copper or 4/0 AWG aluminum. NEC 230.79 allows 100A minimum but 200A is standard practice.

The 80% Rule (NEC 210.20)

A 200 Amp breaker has a maximum continuous load of 160A (200A × 80%). Continuous loads are those expected to run for 3 hours or more. If your load exceeds 160A continuously, upsize to the next standard breaker size. Non-continuous loads can use the full 200A rating.

Wire Sizing (NEC 310.16)

Per NEC Table 310.16 at 75°C: a 200 Amp breaker requires 3/0 AWG copper conductor minimum. For aluminum, upsize two gauges. For runs exceeding 75 feet, use 4/0 AWG to keep voltage drop under 3%. Verify with our Wire Size Calculator and Voltage Drop Calculator.

Common Uses for 200 Amp Circuits

Modern main service panel — most common residential.

Disclaimer: This guide is for reference. All electrical work must be verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions

All Breaker Sizes — Wire & Load Reference

BreakerWireMax Cont.Max W (240V)
15 Amp14 AWG12A2,880W
20 Amp12 AWG16A3,840W
25 Amp10 AWG20A4,800W
30 Amp10 AWG24A5,760W
40 Amp8 AWG32A7,680W
50 Amp6 AWG40A9,600W
60 Amp6 AWG48A11,520W
70 Amp4 AWG56A13,440W
80 Amp3 AWG64A15,360W
100 Amp1 AWG80A19,200W
125 Amp1/0 AWG100A24,000W
150 Amp2/0 AWG120A28,800W
200 Amp3/0 AWG160A38,400W
300 Amp350 MCM240A57,600W
400 Amp500 MCM320A76,800W