300 Amp Breaker — Wire Size, Max Load & NEC Guide

A 300 Amp breaker requires 350 MCM copper wire. Max continuous load: 240A (80% rule). Max watts: 28,800W at 120V or 57,600W at 240V.

300 Amp Breaker Specifications
350 MCM Wire
Breaker
300A
Wire Size
350 MCM
Max Continuous
240A
Max Watts (120V)
28,800W
Max Watts (240V)
57,600W
Long Run Wire
500 MCM
NEC Reference
NEC 230.79

300 Amp Breaker — Complete NEC Guide

300A services are used in large homes with all-electric heating, multiple EV chargers, and pools/hot tubs. Typically requires 350 MCM copper or 500 MCM aluminum. May use parallel conductors.

The 80% Rule (NEC 210.20)

A 300 Amp breaker has a maximum continuous load of 240A (300A × 80%). Continuous loads are those expected to run for 3 hours or more. If your load exceeds 240A continuously, upsize to the next standard breaker size. Non-continuous loads can use the full 300A rating.

Wire Sizing (NEC 310.16)

Per NEC Table 310.16 at 75°C: a 300 Amp breaker requires 350 MCM copper conductor minimum. For aluminum, upsize two gauges. For runs exceeding 75 feet, use 500 MCM to keep voltage drop under 3%. Verify with our Wire Size Calculator and Voltage Drop Calculator.

Common Uses for 300 Amp Circuits

Large homes, multi-family, light commercial.

Disclaimer: This guide is for reference. All electrical work must be verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions

All Breaker Sizes — Wire & Load Reference

BreakerWireMax Cont.Max W (240V)
15 Amp14 AWG12A2,880W
20 Amp12 AWG16A3,840W
25 Amp10 AWG20A4,800W
30 Amp10 AWG24A5,760W
40 Amp8 AWG32A7,680W
50 Amp6 AWG40A9,600W
60 Amp6 AWG48A11,520W
70 Amp4 AWG56A13,440W
80 Amp3 AWG64A15,360W
100 Amp1 AWG80A19,200W
125 Amp1/0 AWG100A24,000W
150 Amp2/0 AWG120A28,800W
200 Amp3/0 AWG160A38,400W
300 Amp350 MCM240A57,600W
400 Amp500 MCM320A76,800W