UK WiringApril 3, 2026 · 10 min read · UK

Cable Size Calculator UK — BS 7671 Guide IET Wiring Regulations 2026

Cable sizing in the UK follows BS 7671 (IET Wiring Regulations), which specifies current-carrying capacity, voltage drop limits, and correction factors for installation conditions. The most common domestic cables are 1.0mm² for lighting (6A), 2.5mm² for ring finals (32A), and 6.0mm² for cookers and EV chargers (32-45A). This guide covers sizing for all common UK domestic circuits.

Cable Size Calculator UK BS 7671
UK Cable Sizing (BS 7671)
Table 4D5A
1.0mm² lighting · 2.5mm² ring · 6.0mm² cooker/EV · Correction factors apply
Lighting
1.0mm²
Ring Main
2.5mm²
Cooker
6.0mm²
Shower 10kW
10.0mm²

BS 7671 Cable Current Ratings (Table 4D5A)

The current-carrying capacity of cables depends on the installation method. For twin & earth (T&E) cable clipped direct (Reference Method C per BS 7671): 1.0mm²: 15.5A. 1.5mm²: 20A. 2.5mm²: 27A. 4.0mm²: 37A. 6.0mm²: 47A. 10.0mm²: 65A. 16.0mm²: 87A. These ratings apply at 30°C ambient with no grouping or insulation correction. In reality, you must apply correction factors that reduce these ratings.

Correction Factors — Ca, Cg, Ci

BS 7671 requires applying correction factors to account for real installation conditions: Ca (ambient temperature): At 30°C = 1.00 (standard). At 35°C = 0.94. At 40°C = 0.87. Loft spaces in summer can reach 40°C+. Cg (grouping): Multiple cables bundled together reduce capacity. 2 cables = 0.80. 3 cables = 0.70. 4+ = further reduction per Table 4C1. Ci (thermal insulation): Cable touching insulation: 0.75. Cable enclosed in insulation: 0.50. The corrected current = Table rating × Ca × Cg × Ci. Use our Wire Size Calculator.

BS 7671 Cable Reference

Common UK Domestic Circuits

Lighting circuit (6A MCB): 1.0mm² T&E. Max 10-12 light points per circuit. CPC (earth): 1.0mm². Ring final (32A MCB): 2.5mm² T&E forming a ring. Serves general sockets in one floor/area. Maximum floor area: 100m². Radial socket (20A MCB): 2.5mm² T&E. Alternative to ring for smaller areas (up to 50m²). Cooker circuit (32-45A): 6.0mm² T&E on 32A MCB (most cookers) or 10.0mm² on 45A MCB (large range cookers). Electric shower (40-50A): 10.0mm² on 45A or 50A MCB for 9.5-10.5 kW showers. EV charger (32A): 6.0mm² on 40A Type C MCB per IET Code of Practice.

Voltage Drop Calculations

BS 7671 limits voltage drop to 5% of nominal voltage (230V × 5% = 11.5V) for the total circuit, with 3% recommended for lighting. Voltage drop per metre per amp is given in the cable tables: 1.0mm² T&E: 44 mV/A/m. 2.5mm² T&E: 18 mV/A/m. 6.0mm² T&E: 7.3 mV/A/m. 10.0mm² T&E: 4.4 mV/A/m. Formula: VD = (mV/A/m × Design Current × Length) ÷ 1000. For a 32A cooker on 6.0mm² at 15m: VD = (7.3 × 32 × 15) ÷ 1000 = 3.5V (1.5% — acceptable).

Cable Size by Circuit
Cable SizeCurrent RatingTypical CircuitMCB Size
1.0mm²15.5ALighting6A Type B
1.5mm²20AImmersion heater16A Type B
2.5mm²27ARing final / Radial32A / 20A
4.0mm²37ALarge radial32A
6.0mm²47ACooker, EV charger32-40A
10.0mm²65AHigh-power shower, sub-main45-50A
16.0mm²87ASub-main, large loads63-80A

EV Charger Cable Sizing per IET Code of Practice

The IET Code of Practice for EV Charging specifies: a 7kW (32A) home charger requires a dedicated radial circuit with 6.0mm² T&E cable, a 40A Type C MCB, and a Type A or Type B RCD (30mA). The cable must be sized accounting for correction factors — if the cable passes through insulated areas (loft, wall cavities), use Ci = 0.75, which may require upsizing to 10.0mm². PME earth considerations: if TN-C-S (PME) supply, additional earthing requirements per BS 7671 722.411.4.1 apply. Many installers use an earth rod as additional protection.

BS 7671 Cable Rules

Disclaimer: For educational reference only. Consult a licensed professional.

Frequently Asked Questions

What cable do I need for a UK ring main?
2.5mm² twin and earth (T&E) cable on a 32A MCB, forming a ring. Maximum floor area: 100m² per BS 7671.
What cable size for a cooker in the UK?
6.0mm² on a 32A MCB for most cookers. Large range cookers (over 13kW) may need 10.0mm² on a 45A MCB.
What cable for a UK EV charger?
6.0mm² T&E on a 40A Type C MCB with RCD protection per IET Code of Practice. May need 10.0mm² if passing through insulation.
What are BS 7671 correction factors?
Multipliers that reduce cable ratings for: ambient temperature (Ca), cable grouping (Cg), and thermal insulation (Ci). All three must be applied.
What is the voltage drop limit in BS 7671?
5% of 230V (11.5V) for the total circuit. 3% recommended for lighting circuits. Calculate using mV/A/m values from cable tables.