1-1/4 Inch Conduit Fill Chart

How many wires fit in 1-1/4" conduit? See the complete THHN wire fill chart for 1-1/4" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: 4-8 circuits, small sub-panel feeds.

1-1/4" Conduit Specifications
1-1/4" (1.25" trade size)
EMT Area
0.49 sq in
PVC Area
0.52 sq in
40% Fill
0.196 sq in
31% Fill
0.152 sq in
Common Use
4-8 circuits

THHN Wire Fill Chart — 1-1/4" EMT Conduit

Wire SizeMax Wires (40% fill)
#6 THHN10 wires
#8 THHN13 wires
#10 THHN23 wires
#12 THHN37 wires
#14 THHN50 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 1-1/4" Conduit

4-8 circuits, small sub-panel feeds. This size is used for larger residential and light commercial installations. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.