3-1/2 Inch Conduit Fill Chart

How many wires fit in 3-1/2" conduit? See the complete THHN wire fill chart for 3-1/2" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: Large commercial feeders.

3-1/2" Conduit Specifications
3-1/2" (3.5" trade size)
EMT Area
2.876 sq in
PVC Area
2.99 sq in
40% Fill
1.15 sq in
31% Fill
0.891 sq in
Common Use
Large commercial feeders

THHN Wire Fill Chart — 3-1/2" EMT Conduit

Wire SizeMax Wires (40% fill)
#2 THHN28 wires
#4 THHN38 wires
#6 THHN55 wires
#8 THHN77 wires
#1/0 THHN19 wires
#2/0 THHN16 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 3-1/2" Conduit

Large commercial feeders. This is a commercial/industrial size for large feeders and service entrance conductors. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.