3/4 Inch Conduit Fill Chart

How many wires fit in 3/4" conduit? See the complete THHN wire fill chart for 3/4" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: 2-4 circuits, residential branch circuits.

3/4" Conduit Specifications
3/4" (0.75" trade size)
EMT Area
0.213 sq in
PVC Area
0.228 sq in
40% Fill
0.085 sq in
31% Fill
0.066 sq in
Common Use
2-4 circuits

THHN Wire Fill Chart — 3/4" EMT Conduit

Wire SizeMax Wires (40% fill)
#8 THHN6 wires
#10 THHN10 wires
#12 THHN16 wires
#14 THHN22 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 3/4" Conduit

2-4 circuits, residential branch circuits. This is a common residential size suitable for most branch circuit runs. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.