4 Inch Conduit Fill Chart

How many wires fit in 4" conduit? See the complete THHN wire fill chart for 4" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: Large industrial feeders, service mains.

4" Conduit Specifications
4" (4" trade size)
EMT Area
3.694 sq in
PVC Area
3.85 sq in
40% Fill
1.478 sq in
31% Fill
1.145 sq in
Common Use
Large industrial feeders

THHN Wire Fill Chart — 4" EMT Conduit

Wire SizeMax Wires (40% fill)
#2 THHN35 wires
#4 THHN49 wires
#6 THHN70 wires
#1/0 THHN24 wires
#2/0 THHN21 wires
#3/0 THHN18 wires
#4/0 THHN15 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 4" Conduit

Large industrial feeders, service mains. This is a commercial/industrial size for large feeders and service entrance conductors. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.