2 Inch Conduit Fill Chart

How many wires fit in 2" conduit? See the complete THHN wire fill chart for 2" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: Large panel feeds, multiple circuits, service entrance.

2" Conduit Specifications
2" (2" trade size)
EMT Area
1.049 sq in
PVC Area
1.1 sq in
40% Fill
0.42 sq in
31% Fill
0.325 sq in
Common Use
Large panel feeds

THHN Wire Fill Chart — 2" EMT Conduit

Wire SizeMax Wires (40% fill)
#2 THHN10 wires
#3 THHN12 wires
#4 THHN14 wires
#6 THHN20 wires
#8 THHN28 wires
#10 THHN49 wires
#12 THHN78 wires
#14 THHN108 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 2" Conduit

Large panel feeds, multiple circuits, service entrance. This size is used for larger residential and light commercial installations. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.