1/2 Inch Conduit Fill Chart

How many wires fit in 1/2" conduit? See the complete THHN wire fill chart for 1/2" EMT, PVC, and rigid conduit per NEC Chapter 9 Table C1. Common uses: 1-2 circuits, low-voltage, data cables.

1/2" Conduit Specifications
1/2" (0.5" trade size)
EMT Area
0.122 sq in
PVC Area
0.131 sq in
40% Fill
0.049 sq in
31% Fill
0.038 sq in
Common Use
1-2 circuits

THHN Wire Fill Chart — 1/2" EMT Conduit

Wire SizeMax Wires (40% fill)
#8 THHN3 wires
#10 THHN5 wires
#12 THHN9 wires
#14 THHN12 wires

Based on NEC Chapter 9 Table C1 for EMT conduit with THHN/THWN-2 conductors at 40% fill (3+ conductors).

NEC Conduit Fill Rules

1 conductor: 53% of conduit area. 2 conductors: 31% of conduit area. 3+ conductors: 40% of conduit area. These rules are per NEC Chapter 9 Table 1 and apply to all conduit types (EMT, PVC, rigid).

Equipment grounding conductors count toward fill but not toward ampacity derating. Bare grounds use less area than insulated conductors of the same gauge.

When to Use 1/2" Conduit

1-2 circuits, low-voltage, data cables. This is a common residential size suitable for most branch circuit runs. Use our Conduit Fill Calculator for exact fill calculations with mixed wire sizes.

Disclaimer: Based on NEC Chapter 9 tables. Verify with local codes. Consult a licensed electrician.