What Size Breaker for Air Conditioner?

A air conditioner requires a 30A breaker with 10 AWG wire on a 240V dedicated circuit. This is a continuous load — breaker rated at 125% of actual draw.

Air Conditioner Wiring Requirements
30A / 10 AWG
Breaker
30A
Wire Size
10 AWG
Voltage
240V
Typical Draw
30A
Wattage
3,500W
Load Type
Continuous
Circuit
Dedicated
NEC Ref
NEC 440.22

🔌 Wire Length & Voltage Drop Check

50 ft
Voltage Drop
1.25%
Drop (Volts)
3.00V
Rec. Wire
10 AWG

Air Conditioner Wiring Guide — NEC Requirements

Central AC units require a dedicated 240V circuit. Window units under 15A can use a standard 120V/15A circuit. Size breaker per NEC 440.22 based on compressor nameplate MCA (Minimum Circuit Ampacity).

Pro Tip

💡 Check the unit nameplate for MCA and MOP (Maximum Overcurrent Protection). The breaker must not exceed the MOP rating.

Why a 30A Breaker?

The air conditioner draws approximately 30A at 240V (3500W). As a continuous load (3+ hours), NEC 210.20 requires the breaker at 125%: 30A × 1.25 = 37.5A → 30A breaker.

Wire Sizing per NEC 310.16

For a 30A/240V circuit, 10 AWG copper is required per NEC Table 310.16 at 75°C. For runs over 75 feet, upsize to 8 AWG (long runs). Use our Wire Size Calculator and Voltage Drop Calculator.

Complete Parts List

To wire a air conditioner circuit: a 30A double-pole breaker, 10 AWG NM-B cable (Romex) for interior runs or THHN/THWN-2 in conduit for exposed runs, a NEMA 14-30 receptacle (or hardwired), cable clamps, and appropriate junction boxes.

Disclaimer: This guide is for reference only. All electrical work must be performed by or verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions