What Size Breaker for Electric Range / Oven?

A electric range / oven requires a 50A breaker with 6 AWG wire on a 240V dedicated circuit.

Electric Range / Oven Wiring Requirements
50A / 6 AWG
Breaker
50A
Wire Size
6 AWG
Voltage
240V
Typical Draw
40A
Wattage
9,600W
Load Type
Non-Continuous
Circuit
Dedicated
NEC Ref
NEC 220.55

🔌 Wire Length & Voltage Drop Check

50 ft
Voltage Drop
0.66%
Drop (Volts)
1.58V
Rec. Wire
6 AWG

Electric Range / Oven Wiring Guide — NEC Requirements

Electric ranges typically require a 40A or 50A/240V dedicated circuit. NEC 220.55 allows demand factors for household cooking equipment. The receptacle must be NEMA 14-50 (4-prong).

Pro Tip

💡 Most modern ranges need a 50A circuit. Check the range nameplate — some smaller units only need 40A.

Why a 50A Breaker?

The electric range / oven draws approximately 40A at 240V (9600W). A 50A breaker provides adequate protection.

Wire Sizing per NEC 310.16

For a 50A/240V circuit, 6 AWG copper is required per NEC Table 310.16 at 75°C. For runs over 75 feet, upsize to 4 AWG (runs over 50ft). Use our Wire Size Calculator and Voltage Drop Calculator.

Complete Parts List

To wire a electric range / oven circuit: a 50A double-pole breaker, 6 AWG NM-B cable (Romex) for interior runs or THHN/THWN-2 in conduit for exposed runs, a NEMA 14-50 receptacle (or hardwired), cable clamps, and appropriate junction boxes.

Disclaimer: This guide is for reference only. All electrical work must be performed by or verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions