What Size Breaker for Electric Furnace?

A electric furnace requires a 60A breaker with 6 AWG wire on a 240V dedicated circuit. This is a continuous load — breaker rated at 125% of actual draw.

Electric Furnace Wiring Requirements
60A / 6 AWG
Breaker
60A
Wire Size
6 AWG
Voltage
240V
Typical Draw
60A
Wattage
15,000W
Load Type
Continuous
Circuit
Dedicated
NEC Ref
NEC 424.3

🔌 Wire Length & Voltage Drop Check

50 ft
Voltage Drop
0.99%
Drop (Volts)
2.37V
Rec. Wire
6 AWG

Electric Furnace Wiring Guide — NEC Requirements

Electric furnaces are continuous loads and may require 40A to 100A circuits depending on heating capacity. Multi-element furnaces may need multiple circuits.

Pro Tip

💡 Check the furnace nameplate for exact amperage. Some units require two separate circuits for different heating elements.

Why a 60A Breaker?

The electric furnace draws approximately 60A at 240V (15000W). As a continuous load (3+ hours), NEC 210.20 requires the breaker at 125%: 60A × 1.25 = 75.0A → 60A breaker.

Wire Sizing per NEC 310.16

For a 60A/240V circuit, 6 AWG copper is required per NEC Table 310.16 at 75°C. For runs over 75 feet, upsize to 4 AWG. Use our Wire Size Calculator and Voltage Drop Calculator.

Complete Parts List

To wire a electric furnace circuit: a 60A double-pole breaker, 6 AWG NM-B cable (Romex) for interior runs or THHN/THWN-2 in conduit for exposed runs, a NEMA 14-50 receptacle (or hardwired), cable clamps, and appropriate junction boxes.

Disclaimer: This guide is for reference only. All electrical work must be performed by or verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions