What Size Breaker for Sump Pump?

A sump pump requires a 15A breaker with 14 AWG wire on a 120V dedicated circuit.

Sump Pump Wiring Requirements
15A / 14 AWG
Breaker
15A
Wire Size
14 AWG
Voltage
120V
Typical Draw
8A
Wattage
960W
Load Type
Non-Continuous
Circuit
Dedicated
NEC Ref
NEC 210.8

🔌 Wire Length & Voltage Drop Check

50 ft
Voltage Drop
1.68%
Drop (Volts)
2.02V
Rec. Wire
14 AWG

Sump Pump Wiring Guide — NEC Requirements

Sump pumps should be on a dedicated 15A or 20A/120V circuit. GFCI protection is required per NEC 210.8 for basement/crawl space receptacles, but this can cause nuisance tripping.

Pro Tip

💡 Consider a GFCI breaker rather than a GFCI outlet to reduce nuisance tripping. Battery backup sump pumps are recommended.

Why a 15A Breaker?

The sump pump draws approximately 8A at 120V (960W). A 15A breaker provides adequate protection.

Wire Sizing per NEC 310.16

For a 15A/120V circuit, 14 AWG copper is required per NEC Table 310.16 at 75°C. For runs over 75 feet, upsize to 12 AWG. Use our Wire Size Calculator and Voltage Drop Calculator.

Complete Parts List

To wire a sump pump circuit: a 15A single-pole breaker, 14 AWG NM-B cable (Romex) for interior runs or THHN/THWN-2 in conduit for exposed runs, a NEMA 5-15 or 5-20 receptacle, cable clamps, and appropriate junction boxes.

Disclaimer: This guide is for reference only. All electrical work must be performed by or verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions