What Size Breaker for Dishwasher?

A dishwasher requires a 15A breaker with 14 AWG wire on a 120V dedicated circuit.

Dishwasher Wiring Requirements
15A / 14 AWG
Breaker
15A
Wire Size
14 AWG
Voltage
120V
Typical Draw
10A
Wattage
1,200W
Load Type
Non-Continuous
Circuit
Dedicated
NEC Ref
NEC 422.12

🔌 Wire Length & Voltage Drop Check

50 ft
Voltage Drop
2.10%
Drop (Volts)
2.52V
Rec. Wire
14 AWG

Dishwasher Wiring Guide — NEC Requirements

Dishwashers require a dedicated 15A or 20A/120V circuit per NEC. Most modern dishwashers draw 10-12A. Many electricians install 20A circuits with 12 AWG wire for future flexibility.

Pro Tip

💡 The dishwasher circuit can share with a garbage disposal per NEC if using a 20A circuit with 12 AWG wire.

Why a 15A Breaker?

The dishwasher draws approximately 10A at 120V (1200W). A 15A breaker provides adequate protection.

Wire Sizing per NEC 310.16

For a 15A/120V circuit, 14 AWG copper is required per NEC Table 310.16 at 75°C. For runs over 75 feet, upsize to 12 AWG (recommended). Use our Wire Size Calculator and Voltage Drop Calculator.

Complete Parts List

To wire a dishwasher circuit: a 15A single-pole breaker, 14 AWG NM-B cable (Romex) for interior runs or THHN/THWN-2 in conduit for exposed runs, a NEMA 5-15 or 5-20 receptacle, cable clamps, and appropriate junction boxes.

Disclaimer: This guide is for reference only. All electrical work must be performed by or verified by a licensed electrician. Local codes may differ from NEC.

Frequently Asked Questions